Pacific FW120 Fire Window -/120/-

 

The Pacific FW120 is a fire window system which is fire resisting glazing as defined in the New Zealand Building Code Acceptable Solutions C/AS2 to C/AS6.

The system consists of non-opening (fixed) glazing with Pyroceram clear glass factory-fitted into a steel frame for interior use.

Glazing Type Maximum Glazed Area Max Height (mm) Max Width (mm) Frame Type Fire Rating
Timber Steel
Pyroceram 1.28 m2 845 1515   -/120/-
Pyroceram 1.28 m2 1515 845   -/120/-

Notes:  

  1. Sizes noted above are the clear view.
  2. The height and width is interchangeable as shown below.

Product Options

Frame Types & Profiles

Timber Frame

The FW120 is not available in a timber frame.

Steel Frame

Pressed steel or stainless steel 1.6mm. Profile may be single or double rebated with 38mm reveal (minimum).

For more in depth information on frame profiles and sizes, please see our Installation Instructions.

Wall Types

  • Non-load bearing timber stud/Gib Board® wall conforming to minimum specification GBT120a or GBT120b as listed in “Gib® Fire Rated Systems 1997”.
  • Non-load bearing steel stud wall conforming to minimum specification GBS120 (“Gib® Fire Rated Systems 1997”).
  • Masonry or concrete construction.

Product Optional Extras

Exterior Situations

FW120 is intended for interior use in dry conditions.

Additional Features

The FW120 may not be connected to a door frame as a sidelight or highlight. A wall segment of minimum width 250mm must separate the FW120 fire window from a door set or neighbouring window frame.

Building Product Information Statement