Pacific VP30A Hinged Door Set -/30/30sm Installation

 

This tool is designed to filter the available results as you search. Once you have applied a filter, you may need to reset the filter to be able to see all other available options.

To see our installation videos please click here.

Installation wall framing requirements

Pacific VP30A Hinged Door Set -/30/30sm

WALL TYPE: Timber stud
FRAME TYPE: Timber

Frame materials available:

  • Hardwoods of minimum density 580 kg/m3 (minimum thickness is 30mm)

Fasteners:

  • Frame - Either nailed (75 x 3.2mm) or screwed (10g x 75mm) at 600mm centres nominal. Two fixings per location.
  • Stops - nailed (50 x 3.2mm) at 200mm centres.
  • Architrave - nailed (50 x 3.2mm) at 400mm centres.
  • Pryda Jamb-fixa brackets Type JFB100 at 500mm centres may be used to fix profiles A & B to approved walls.

Head Fixing (minimum):

  • Single door - none required
  • Paired door - double central fastener required

Stud size:

  • Ex 75 x 50 minimum.

Wedging gap:

  • 0-10mm
F-D-VP30A-T-T-1 image
WALL TYPE: Timber stud
FRAME TYPE: Timber

Frame materials available:

  • Hardwood of minimum density 580 kg/m3 (minimum thickness is 30mm)

Fasteners:

  • Frame - Either nailed (75 x 3.2mm) or screwed (10g x 75mm) at 600mm centres nominal. Two fixings per location.
  • Stops - nailed (50 x 3.2mm) at 200mm centres.
  • Architrave - nailed (50 x 3.2mm) at 400mm centres.
  • Pryda Jamb-fixa brackets Type JFB100 at 500mm centres may be used to fix profiles A & B to approved walls.

Head Fixing (minimum):

  • Single door - none required
  • Paired door - double central fastener required

Stud size:

  • Ex 75 x 50 minimum.

Wedging gap:

  • 0-10mm
F-D-VP30A-T-T-2 image
WALL TYPE: Timber stud
FRAME TYPE: Timber

Frame materials available:

  • Hardwood of minimum density 580 kg/m3 (minimum thickness is 30mm)

Fasteners:

  • Frame - Either nailed (75 x 3.2mm) or screwed (10g x 75mm) at 600mm centres. Two fixings per location.
  • Stops - nailed (50 x 3.2mm) at 200mm centres.
  • Architrave - nailed (50 x 3.2mm) at 400mm centres.

Head Fixing (minimum):

  • Single door - none required
  • Paired door - double central fastener required

Stud size:

  • Ex 75 x 50 minimum.

Wedging gap:

  • 0-15mm
F-D-VP30A-T-T-3 image
WALL TYPE: Timber stud
FRAME TYPE: Steel, 1-part

Frame materials available:

  • EGZ - 1.6mm
  • Cold rolled galvanized - 1.6mm
  • Stainless Steel - 1.5mm

Fasteners:

  • Folded steel connection plates (as shown) to be supplied with frames.
  • Hook onto frame bracing straps and nail or screw to timber studs.
  • Frame connection plates either clouts (30 x 2.5mm gib clouts) or screw fixed.

Head Fixing (minimum):

  • Single door - none required
  • Paired door - single central fastener required

Stud size:

  • Ex 100 x 50 minimum

Wedging gap:

  • Not applicable

Insulation rating:

To obtain an insulation rating, the steel frame must be packed with either;

  • Plasterboard (30 minutes)
  • Ceramic fibre blanket (30 minutes)
  • Cornice plaster (30 minutes)
  • Grout (60 minutes)
  • Pyropanel M4 mortar (60 minutes)

No frame packing equals no insulation rating (i.e. -/xx/-)

F-D-VP30_VP60-S-T-1 image
WALL TYPE: Timber stud
FRAME TYPE: Steel, 1-part

Frame materials available:

  • EGZ - 1.6mm
  • Cold rolled galvanized - 1.6mm
  • Stainless Steel - 1.5mm

Fasteners:

  • Framing stud No.1 screwed to jamb.
  • Connection to stud No.2 via rebated nail on plates. One fastener per location except at bottom where two fasteners are required.
  • Frame to be screw fixed (10g self tapping) at 600mm nominal centres. Two fasteners per location where applicable.

Head Fixing (minimum):

  • Single door - none required
  • Paired door - double central fastener required

Stud size:

  • Ex 100x50 minimum

Wedging gap:

  • Not applicable

Insulation rating:

To obtain an insulation rating, the steel frame must be packed with either;

  • Plasterboard (30 minutes)
  • Ceramic fibre blanket (30 minutes)
  • Cornice plaster (30 minutes)
  • Grout (60 minutes)
  • Pyropanel M4 mortar (60 minutes)

No frame packing equals no insulation rating (i.e. -/xx/-)

F-D-VP30_VP60-S-T-2 image
WALL TYPE: Timber stud
FRAME TYPE: Steel, 1-part

Frame materials available:

  • EGZ - 1.6mm
  • Cold rolled galvanized - 1.6mm
  • Stainless Steel - 1.5mm

Fasteners:

  • Frame screwed to stud through Gib Fyreline packing between stud and shims.
  • Frame to be screw fixed (10g self tapping) at 600mm nominal centres. Two fasteners per location where applicable.

Head Fixing (minimum):

  • Single door - none required
  • Paired door - double central fastener required

Stud size:

  • Ex 100 x 50 minimum

Wedging gap:

  • 0-10mm

Insulation rating:

To obtain an insulation rating, the steel frame must be packed with either;

  • Plasterboard (30 minutes)
  • Ceramic fibre blanket (30 minutes)
  • Cornice plaster (30 minutes)
  • Grout (60 minutes)
  • Pyropanel M4 mortar (60 minutes)

No frame packing equals no insulation rating (i.e. -/xx/-)

F-D-VP30_VP60-S-T-3 image
WALL TYPE: Timber stud
FRAME TYPE: Steel, 1-part

Frame materials available:

  • EGZ - 1.6mm
  • Cold rolled galvanized - 1.6mm
  • Stainless Steel - 1.5mm

Fasteners:

  • Frames may be screwed directly to studs either through the stud and into the frame bracing straps or through the frame into the timber stud at 600mm centres nominal.
  • Frame to be screw fixed (10g self tapping) at 600mm centres nominal. Two fasteners per location where applicable.

Head Fixing (minimum):

  • Single door - none required
  • Paired door - double central fastener required

Stud size:

  • Ex 100 x 50 minimum

Wedging gap:

  • Not applicable

Insulation rating:

To obtain an insulation rating, the steel frame must be packed with either;

  • Plasterboard (30 minutes)
  • Ceramic fibre blanket (30 minutes)
  • Cornice plaster (30 minutes)
  • Grout (60 minutes)
  • Pyropanel M4 mortar (60 minutes)

No frame packing equals no insulation rating (i.e. -/xx/-)

F-D-VP30_VP60-S-T-4 image
WALL TYPE: Timber stud
FRAME TYPE: Steel, 2-part

Frame materials available:
* EGZ - 1.6mm
* Cold rolled galvanized - 1.6mm
* Stainless Steel - 1.5mm

Fasteners:

  • Frame to be screw fixed (10g self tapping through frame straps, timber packers and into timber stud. Standard is 4 No. per Jamb (Front section), 2 No. Per Jamb (Rear section)

Head Fixing (minimum):

  • Single door - none required
  • Paired door - 2 No. fasteners required (Front section only)

Stud size:

  • Ex 100x50 minimum

Wedging gap:

  • Not applicable

Insulation rating:

To obtain an insulation rating, the steel frame must be packed with either;

  • Plasterboard (30 minutes)
  • Ceramic fibre blanket (30 minutes)
  • Cornice plaster (30 minutes)
  • Grout (60 minutes)
  • Pyropanel M4 mortar (60 minutes)

No frame packing equals no insulation rating (i.e. -/xx/-)

F-D-VP30_ 60 2 Part-S-T-1 image
WALL TYPE: Timber stud
FRAME TYPE: Steel, 2-part
F-D-VP30_ 60 2 Part-S-T-2 image
WALL TYPE: Timber stud
FRAME TYPE: Steel, 2-part

Frame materials available:

  • EGZ - 1.6mm
  • Cold rolled galvanized - 1.6mm

Fasteners:

  • Frame to be screw fixed (10g self tapping) at 600mm nominal centres through frame straps and timber packers into timber stud.
  • Standard is 4 no. per jamb (front section) and 2 no. per jamb (rear section)

Head Fixing (minimum):

  • Single door - none required
  • Paired door - 2 no. fasteners required (front section only)

Stud size:

  • Ex 100 x 50 minimum

Wedging gap:

  • 0-10mm

Insulation rating:

To obtain an insulation rating, all voids in the steel frame and wedging gaps must be packed with either;

  • Plasterboard (30 minutes)
  • Ceramic fibre blanket, 96 kg/m3 min. (30 minutes)
  • Mineral wool blanket, 96 kg/m3 min. (30 minutes)

No frame packing equals no insulation rating (i.e. -/xx/-)

F-D-VP30_60 2 Part-S-T-1 image
WALL TYPE: Masonry
FRAME TYPE: Timber

Frame materials available:

  • Hardwood of minimum density 580 kg/m3 (minimum thickness is 30mm)

Fasteners:

  • Frame - M8 or M10 'Ramset' Dynabolts at 600mm centres nominal. Fixings on or near centre of frame jamb.
  • Stops - nailed (50 x 3.2mm) at 200mm centres.
  • Architrave -nailed (50 x 3.2mm) at 400mm centres.

Head Fixing (minimum):

  • Single door - none required
  • Paired door - single central fastener required

Wedging gap:

  • 0-15mm
F-D-VP30A-T-M image
WALL TYPE: Masonry
FRAME TYPE: Steel, 1-part

Frame materials available:

  • EGZ - 1.6mm
  • Cold rolled galvanized - 1.6mm
  • Stainless Steel - 1.5mm (Must be fully grouted frame VP90-120)

Fasteners:

  • Jamb fixing at 600mm centres minimum
  • Expansion anchors eg. M10 countersunk 'Ramset' Dynabolts
  • M12 countersunk masonry screwbolts

Head Fixing (minimum):

  • Single door - none required
  • Paired door - single central fastener required

Wedging Gap:

  • 0-15mm

Insulation rating:

To obtain an insulation rating, the steel frame must be packed with either;

  • Plasterboard (30 minutes)
  • Ceramic fibre blanket (30 minutes)
  • Cornice plaster (30 minutes)
  • Grout (60 minutes)
  • Pyropanel M4 mortar (60 minutes)

No frame packing equals no insulation rating (i.e. -/xx/-)

F-D-VP30_VP120-S-M image
WALL TYPE: Masonry
FRAME TYPE: Steel, 2-part

Frame materials available:

  • EGZ - 1.6mm
  • Cold rolled galvanized - 1.6mm
  • Stainless Steel - 1.5mm

Fasteners:

  • Frame to be fixed with masonry anchors or screw bolts. Standard is 4 No. per Jamb. Rear insert fixed to frame with machine screws (drilled and tapped on site).

Head Fixing (minimum):

  • Single door - none required
  • Paired door - 2 No. fasteners required (Front section only)

Wedging gap:

  • Not applicable

Insulation rating:


To obtain an insulation rating, the steel frame must be packed with either;

  • Plasterboard (30 minutes)
  • Ceramic wool, 96 kg/m3 (30 minutes)

No frame packing equals no insulation rating (i.e. -/xx/-)

 

F-D-VP30_60 2 part-S-M image
WALL TYPE: Steel stud
FRAME TYPE: Timber

Frame materials available:

  • Hardwood of minimum density 580 kg/m3 (minimum thickness is 30mm)

Fasteners:

  • Frame - Screwed (10g self tapping) at 600mm centres nominal. Minimum of one screw per location. Frames may also be installed by screw fixing the steel studs to the back of the timber frame during wall construction.
  • Stops - nailed (50 x 3.2mm) at 200mm centres.
  • Architrave - nailed (50 x 3.2mm) at 400mm centres.

Head Fixing (minimum):

  • Single door - none required
  • Paired door - double central fastener required

Stud size:

  • 65 x 34mm minimum of 0.55 MSG gauge.

Wedging gap:

  • 0-10mm
F-D-VP30A-T-S-1 image
WALL TYPE: Steel stud
FRAME TYPE: Timber

Frame materials available:

  • Hardwood of minimum density 580 kg/m3 (minimum thickness is 30mm)

Fasteners:

  • Frame - Screwed (10g self tapping) at 600mm centres nominal. Minimum of one screw per location. Frames may also be installed by screw fixing the steel studs to the back of the timber frame during wall construction.
  • Stops - nailed (50 x 3.2mm) at 200mm centres.
  • Architrave - nailed (50 x 3.2mm) at 400mm centres.

Head Fixing (minimum):

  • Single door - none required
  • Paired door - double central fastener required

Stud size:

  • 65 x 34mm minimum of 0.55 MSG gauge.

Wedging gap:

  • 0-10mm
F-D-VP30A-T-S-2 image
WALL TYPE: Steel stud
FRAME TYPE: Timber

Frame materials available:

  • Hardwood timber of minimum density 580 kg/m3 (minimum thickness is 30mm)

Fasteners:

  • Frame - Screwed (10g self tapping) at 600mm centres nominal. Minimum of one screw per location. Frames may also be installed by screw fixing the steel studs to the back of the timber frame during wall construction.
  • Stops - nailed (50 x 3.2mm) at 200mm centres.
  • Architrave - nailed (50 x 3.2mm) at 400mm centres.

Head Fixing (minimum):

  • Single door - none required
  • Paired door - double central fastener required

Stud size:

  • 65 x 34mm minimum of 0.55 MSG gauge.

Wedging gap:

  • 0-10mm
F-D-VP30A-T-S-3 image
WALL TYPE: Steel stud
FRAME TYPE: Steel, 1-part

Frame materials available:

  • EGZ - 1.6mm
  • Cold rolled galvanized - 1.6mm
  • Stainless Steel - 1.5mm

Fasteners:

  • Frame screwed to boxed stud at 600mm centres nominal with self tapping screws.
  • Steel studs may be riveted (steel pop rivets) or screwed (10g self tapping) to the frame bracing straps at 600mm centres nominal.

Head Fixing (minimum):

  • Single door - none required
  • Paired door - double central fastener required

Stud size:

  • 65 x 34mm minimum of 0.55 SMG gauge

Wedging gap:

  • Not applicable

Insulation rating:

To obtain an insulation rating, the steel frame must be packed with either;

  • Plasterboard (30 minutes)
  • Ceramic fibre blanket (30 minutes)
  • Cornice plaster (30 minutes)
  • Grout (60 minutes)
  • Pyropanel M4 mortar (60 minutes)

No frame packing equals no insulation rating (i.e. -/xx/-)

F-D-VP30_VP60-S-S-1 image
WALL TYPE: Steel stud
FRAME TYPE: Steel, 1-part

Frame materials available:

  • EGZ - 1.6mm
  • Cold rolled galvanized - 1.6mm
  • Stainless Steel - 1.5mm

Fasteners:

  • Frame screwed to boxed stud at 600mm centres nominal with self tapping screws.
  • Steel studs may be riveted (steel pop rivets) or screwed (10g self tapping) to the frame bracing straps at 600mm centres nominal.

Head Fixing (minimum):

  • Single door - none required
  • Paired door - double central fastener required

Stud size:

  • 65 x 34mm minimum of 0.55 SMG gauge

Wedging gap:

  • Not applicable

Insulation rating:

To obtain an insulation rating, the steel frame must be packed with either;

  • Plasterboard (30 minutes)
  • Ceramic fibre blanket (30 minutes)
  • Cornice plaster (30 minutes)
  • Grout (60 minutes)
  • Pyropanel M4 mortar (60 minutes)

No frame packing equals no insulation rating (i.e. -/xx/-)

F-D-VP30_VP60-S-S-2 image
WALL TYPE: Steel stud
FRAME TYPE: Steel, 1-part

Frame materials available:

  • EGZ - 1.6mm
  • Cold rolled galvanized - 1.6mm
  • Stainless Steel - 1.5mm

Fasteners:

  • Frame screwed to boxed studs with packing steel shims at 600mm centres nominal.
  • Steel studs may be riveted (steel pop rivets) or screwed (10g self tapping) to the frame bracing straps at 600mm centres nominal.

Head Fixing (minimum):

  • Single door - none required
  • Paired door - double central fastener required

Stud size:

  • 92 x 34mm minimum of 0.55 SMG gauge

Wedging Gap:

  • 0-10mm

Insulation rating:

To obtain an insulation rating, the steel frame must be packed with either;

  • Plasterboard (30 minutes)
  • Ceramic fibre blanket (30 minutes)
  • Cornice plaster (30 minutes)
  • Grout (60 minutes)
  • Pyropanel M4 mortar (60 minutes)

No frame packing equals no insulation rating (i.e. -/xx/-)

F-D-VP30_VP60-S-S-3 image
WALL TYPE: Steel stud
FRAME TYPE: Steel, 2-part

Frame materials available:

  • EGZ - 1.6mm
  • Cold rolled galvanized - 1.6mm

Fasteners:

  • Frame to be screw fixed (10g self tapping) at 600mm nominal centres through frame straps and GiB Fyreline into timber stud.
  • Standard is 4 no. per jamb (front section) and 2 no. per jamb (rear section)

Head Fixing (minimum):

  • Single door - none required
  • Paired door - 2 no. fasteners required (front section only)

Stud size:

  • 65 x 34mm minimum of 0.55 SMG gauge

Wedging gap:

  • 0-10mm

Insulation rating:

To obtain an insulation rating, all voids in the steel frame and wedging gaps must be packed with either;

  • Plasterboard (30 minutes)
  • Ceramic fibre blanket, 96 kg/m3 min. (30 minutes)
  • Mineral wool blanket, 96 kg/m3 min. (30 minutes)

No frame packing equals no insulation rating (i.e. -/xx/-)

F-D-VP30_60 2 Part-S-S-1 image