Pacific VP120-FH Fire Rated Floor Hatch -/120/120

 

The Pacific VP120-FH Fire Rated Floor Hatch consists of one or two proprietary fire rated non-load bearing panels resting in a pressed steel frame. The steel frame is fixed to a concrete floor.

The access hatch permits the installation of relatively large plant into the ceiling cavity or removal of that equipment for maintenance purposes.

Floor hatches are outside the scope of NZS 4520 and are therefore not labelled.

 Configuration Fire Resistance Rating
Stability/Integrity/Insulation
Max Aperture Height (mm) Max Aperture Width (mm) Panel Thickness
 Single panel -/120/120 1700 500 48
Two panel  -/120/120 1700 1275 48

Notes:

  1. Two hatch panels with a removal mullion between are required to achieve clear apertures greater than 1700 x 500mm. The hatch panel frame must use a 25mm stop.
  2. A removable steel cover plate is required to obtain 120 minutes of insulation. Insulation rating without the steel plate is limited to 60 minutes.

Product Options

Leaf Facings

  • Ply

Leaf Edges

The leaf edges listed below are available for this panel.

Frame Types & Profiles

Timber Frame

The VP120-FH is not available in a timber frame.

Steel Frame

The steel frame profiles listed below are available for this panel.

Floor / Ceiling Specifications

Concrete, minimum thickness 150mm.

Optional Extras

A reed switch could be fitted to the assembly to monitor closed status.

Lifting eyes may be factory fitted to the panel. Any such hardware should allow for the possibility of fitting load-bearing panels over (see below).

Restrictions

Panel may not be hinged.

The panels are not suitable for any load bearing applications. If safety requirements necessitate load bearing in and around the aperture then chequer plate (or other suitable panel) must be located over the aperture and supported by the floor.

Building Product Information Statement