Installation wall framing requirements
Pacific VP180 Hinged Door Set -/180/60sm
Frame materials available:
- EGZ - 1.6mm
- Cold rolled galvanized - 1.6mm
- Stainless Steel - 1.5mm
Fasteners:
- 10g x 75mm self tapping screws at 600mm centres.
Head Fixings:
- Single door - none required
- Paired door - central fastener required
Stud size:
- ex100 x 50mm.
Wedging Gap:
- N/A
Insulation rating:
To obtain an insulation rating, the steel frame must be packed with either;
- Plasterboard (30 minutes)
- Ceramic fibre blanket (30 minutes)
- Cornice plaster (30 minutes)
- Grout (60 minutes)
- Pyropanel M4 mortar (60 minutes)
No frame packing equals no insulation rating (i.e. -/xx/-)
Frame materials available:
- EGZ - 1.6mm
- Cold rolled galvanized - 1.6mm
- Stainless Steel - 1.5mm
Fasteners:
- Jamb fixing at 600mm centres minimum
- Expansion anchors eg. M10 countersunk 'Ramset' Dynabolts
- M12 countersunk masonry screwbolts
Head Fixing (minimum):
- Single door - none required
- Paired door - single central fastener required
Wedging Gap:
- 10mm
Insulation rating:
To obtain an insulation rating, the steel frame must be packed with either;
- Plasterboard (30 minutes)
- Ceramic fibre blanket (30 minutes)
- Cornice plaster (30 minutes)
- Grout (60 minutes)
- Pyropanel M4 mortar (60 minutes)
No frame packing equals no insulation rating (i.e. -/xx/-)